SYSTEM OVERVIEW
|
|
Voltage compatibility
|
220, 230, 240V (selectable)
|
|
Frequency compatibility
|
50/60Hz
|
|
OUTPUT
|
|
Output VA
|
1050
|
|
Output watts
|
650
|
|
Output nominal voltage
|
220, 230, 240V (selectable)
|
|
Output voltage regulation
|
LINE MODE: Sine wave line voltage 220/230/ 240V (-9% / +5%), BATTERY MODE: Sine wave output 220/230/240V (+/-5%)
|
|
Output frequency regulation
|
LINE MODE: Passes line frequency of +/-10% BATTERY MODE: Inverter output regulated to 50/60Hz (+/- 1Hz)
|
|
Outlet quantity / type
|
8 IEC-C13
|
|
INPUT
|
|
Maximum input amps
|
2.8 (230V), 3.0 (220V), 2.7 (240V)
|
|
Input connection type
|
IEC-C14
|
|
BATTERY
|
|
Full load runtime
|
7 min. (1050VA)
|
|
Half load runtime
|
20 min. (525VA)
|
|
DC system voltage
|
24V DC
|
|
Typical battery lifespan
|
3-6 years depending on usage
|
|
Battery recharge rate
|
4-8 hours to 90%
|
|
Replacement Battery Cartridge
|
RBC24-SLT
|
|
VOLTAGE REGULATION
|
|
Voltage regulation description
|
Automatic voltage regulation (AVR) circuits maintain clean, regulated computer-grade 220/230/240V nominal output, without using battery power, during brownouts as low as 174V and overvoltages as high as 290V
|
|
Overvoltage correction
|
Input voltages between 232-266V (220V), 244-278V (230V) or 254-290V (240V) are reduced by 12%
|
|
Brownout correction
|
Input voltages between 174-198V (220V), 182-206V (230V) or 190-216V (240V) are boosted by 14%
|
|
LEDS ALARMS & SWITCHES
|
|
Front panel LEDs
|
Includes 9 front panel LEDs to indicate line/battery power status, over/under voltage correction, battery charge level (4 LEDs), load percentage (4 LEDs), overload and replace battery.
|
|
Alarms
|
Audible alarms indicate BATTERY MODE (.4 sec. On/4.6 sec. Off) and OVERLOAD (.4 sec. On/ 6 sec. Off), UPS POWERED ON (single .4 sec. On)
|
|
Switches
|
2 front panel mounted switches. POWER ON switch powers UPS on in AC or battery mode when pressed longer than one second. Power on switch also initiates self test when pressed longer than .5 seconds as the UPS is in line power mode. Also serves as an alarm silence when pressed for longer than .5 seconds in battery mode. POWER OFF switch turns UPS off when pressed and held for longer than 1 second. Rear voltage select DIP switches to accept 220/230/240V AC
|
|
SURGE / NOISE SUPPRESSION
|
|
AC surge suppression
|
350 joules
|
|
AC suppression response time
|
Instantaneous
|
|
Dataline suppression
|
Set of 8-wire RJ jacks offers protection for 10baseT network connection with a clamping voltage of 7.5V on pins 1,2,3 & 6, or single line tel/DSL surge suppression starting at 260V on center pins 4 & 5
|
|
EMI / RFI AC noise suppression
|
Yes
|
|
ENVIRONMENTAL
|
|
Operating Temperature
|
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
|
Storage Temperature
|
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
|
|
Relative Humidity
|
0 to 95%, non-condensing
|
|
COMMUNICATIONS
|
|
Network monitoring port
|
Includes 2 built-in monitoring ports, 1 x HID-compliant USB and 1 x DB9. Each port supports on battery, low battery, power restored, AC line voltage, DC battery voltage, load percentage, battery charge current, battery capacity, temperature and line frequency status messaging. Interface supports timed inverter shutoff after unattended shutdown, activate self-test and output power control for delayed or immediate reboot of connected equipment
|
|
Software and cabling included
|
Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with 2 cables, 1 x USB and 1 x DB9
|
|
SNMP compatibility
|
SNMP adapter accessory # SNMPWEBCARD
|
|
WatchDog compatibility
|
Compatible with Tripp Lite's WatchDog Software to restore operation to locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipmentideal for unattended kiosk applications
|
|
LINE / BATTERY TRANSFER
|
|
Transfer time from line power to battery mode
|
4-8 milliseconds
|
|
Low voltage transfer to battery power
|
Switches to battery power as line voltage decreases to 174V (220V), 182V (230V) or 190V (240V) or less. Resets back to line power mode as line voltage increases to 184V (220V), 192V (230V) or 200V (240V)
|
|
High voltage transfer to battery power
|
Switches to battery power as line voltage increases to 266V (220V), 278V (230V) or290V (240V) or higher. Resets back to line power mode as line voltage decreases to 258V (220V), 270V (230V) or 282V (240V)
|
|
CERTIFICATIONS
|
|
Certifications
|
CE/IEC 62040, GOST, SASO, RoHS-Compliant , Class B (Emissions)
|